|
Garage conversion building
regulations: The conversion of a garage into a living space is
treated as a change of part of a building. An application for approval
under the building regulations must be made before work commences. It
is not possible to be precise in the advice we give regarding to garage
conversions as individual circumstances vary. Vogue garage conversion
staff would be pleased to advise you further. The following points must
be considered when converting a garage into a living space
Garage conversion building
regulations Foundations: A foundation may be required to carry
any additional masonry loads such as a new inner leaf to external walls
or the garage door infill. The condition and suitability of the
existing foundation and floor can be checked when the door area is
excavated. There are three accepted ways to build a wall in place of
the garage door. Option one a new foundation the depth of this
foundation will depend on ground conditions. Options two install two
pre-stressed concrete lintels from the footings of each pillar. Options
three install a steel cavity lintel with a minimum bearing of 150mm
each side onto the brickwork.
Garage conversion building
regulations Wall Thickness: If the existing wall is of a single
leaf construction with brick a pier it must be checked for stability
and freedom from defects. If deemed satisfactory then it is likely that
the wall would be considered suitable, subject to its weather
resistance and insulation.
Garage conversion building
regulations weather resistance: A wall of single leaf
construction must be treated to provide satisfactory resistance to the
passage of moisture. A waterproofing compound applied on the internal
face and incorporated into a floor membrane may be an effective way of
achieving this. The provision of an inner leaf to create a cavity wall
will require a cavity tray at the base of the wall and over any
openings. New and existing floors should also have a suitable damp
proof membrane.
Garage conversion building
regulations floors: It is often desirable to increase the floor
height of the existing garage level with the existing ground floor of
the house. This can be achieved by making up the thickness in either
concrete or timber. Concrete can be laid directly onto the existing
slab on a bed of insulation and damp proof membrane. Timber battens
should be tantalised and laid over rigid floor insulation on the
existing slab on a damp proof membrane. A vapour barrier may then be
laid over the joists/under the boarding. The damp proof membrane should
be dressed continuous with any damp proof course to new or existing
walls.
Garage conversion building
regulations insulation: It may be necessary to insulate the
external walls, roof and floor to habitable standards. New Windows
should achieve a U Value of at least 2.0W/m2K for timber or PVC frames
and 2.2W/m2K for metal frames. This can normally be achieved with a
sealed double glazed unit incorporating a 16mm air gap and with an
inner pane of low-E type glass. Walls should be upgraded to provide a U
Value of around 0.35W/m2K. This could be achieved by dry lining the
wall but the performance of each insulation type differs and therefore
further advice should be obtained. Floors should be upgraded to provide
a U Value of around 0.25W/m2K. This can be achieved with 100mm of
polystyrene floor insulation. The roof should also be upgraded to
provide a U Value of around 0.25W/m2K for a flat roof or 0.16W/m2K
where there is a loft.
Garage conversion building
regulations ventilation: Windows must incorporate an open able
area of an area equal to 1/20th of the floor area of the room, and
trickle vents to provide background ventilation of 8000mm2 for a
habitable room (4000mm2 elsewhere. Mechanical Ventilation may also be
required if a kitchen, utility, bathroom or WC is being created.
Garage conversion building
regulations means of escape: Generally a clear opening of
0.33m2 and with an opening width and height of at least 450mm should be
provided if the room could only be accessed via another room. The
bottom of such an opening should be below 1100mm above floor level.
|